Review Article
A Review of Control Techniques and Energy Storage for Inverter-Based Dynamic Voltage Restorer in Grid-Integrated Renewable Sources
Table 15
Comparison of various two-level inverter topologies in DVR.
| Ref. no. | Inverter topology | Energy storage | Injection transformer | Compensation technique | Capabilities | No. of levels | Modulation technique |
| [10] | VSI inverter | Capacitor | Present | — | Only sag | 2 | PWM | [80] | VSI inverter | Constant source | Present | — | Only sag | 2 | Space vector PWM | [134] | VSI inverter | Electrolytic capacitors | Present | PSC | Only sag | 2 | PWM | [200] | 1 − ϕ half-bridge inverter | Capacitor | Not present | — | Only sag | 2 | PWM | [201] | 1 − ϕ full bridge inverter | Constant source | Present | — | Both | 2 | PWM | [205] | 3 − ϕ three wire inverter | Lead-acid batteries | Present | PSC to IPC | Only sag | 2 | Voltage space vector PWM | [206] | 3 − ϕ four-leg inverter | Constant source | Not present | — | Only sag | 2 | — | [207] | 3 − ϕ six-switch inverter | Capacitor | Present | — | Only sag | 2 | — | [208] | 3 − ϕ split capacitor six switch four wire inverter | Lead-acid batteries | Present | PSC to IPC | Only sag | 2 | Voltage space vector projection method | [209] | VSI inverter | Capacitor | Present | — | Only sag | 2 | PWM | [210] | VSI inverter | Constant source | Present | MEC | Only sag | 2 | PWM | [211] | 3 − ϕ three-wire | Lead-acid batteries | Present | PSC to IPC | Only sag | 2 | Space vector PWM | [212] | 3 − ϕ half-bridge inverter | Constant source | Present | PSC | Only sag | 2 | PWM | [213] | VSI inverter | Constant source | Present | PSC and IPC | Both | 2 | Space vector PWM |
|
|