Review Article
A Review of Control Techniques and Energy Storage for Inverter-Based Dynamic Voltage Restorer in Grid-Integrated Renewable Sources
Table 3
Response to abnormal grid voltage and frequency.
| Standard | Voltage (V) | Clearing time (sec) |
| Abnormal response of grid voltage | IEEE 1547 Rule 21 | V < 45% | 0.16 | 45% < V < 60% | 1 | 60% < V < 88% | 2 | 110% < V < 120% | 1 | 120% < V | 0.16 | IEC 61727 | V < 50% | 0.1 | 50% < V < 85% | 2 | 110% < V < 135% | 2 | 135% < V | 0.05 | IEEE 929 | V < 50% | 6 | 50% < V < 88% | 120 | 110% < V < 120% | 120 | 120% < V | 6 | VDE-AR-N-4105 | V < 80% | 0.1 | V > 110% | 0.1 | AS 4777 | V < 200 V | 2 | V > 270 V | 2 |
| Abnormal response of grid frequency | IEEE 1547A Rule 21 | f < 57 | 0.16 | 57 < f < 59.5 | 2 | 60.5 < f < 62 | 2 | 62 < f | 0.16 | IEC 61727 | ±1 | 0.2 | IEEE 929 | f < 59.5 | 6 | f > 60.5 | 6 | VDE-AR-N-4105 | f < 51.5 | 0.1 | f < 47.5 | 0.1 | AS 4777 | f < 45 | 2 | f > 55 | 2 | Rule 21 | f > 60.5 | 0.16 | f < 59.3 | 0.16 |
|
|
|