Assessing rotor condition [5].

Amplitude difference (−dB)Rotor condition

>50In excellent condition
44–50Good condition
38–44Moderate condition
32–38Rotor bar crack may be in initial stage or high resistance in joints
26–32Two rotor bars may be cracked or high resistance in joints
20–26Several bars cracked or rings end