| Parameter | Proposed algorithm | Reference [7] | Reference [8] | Reference [10] | Reference [13] |
| Time to classify fault | Half or less than one cycle | Half cycle | Half cycle | Not reported | Not reported | Input signals used | 3-phase single-ended voltage and current | 3-phase current samples | 3-phase current samples | 3-phase voltage and current | 3-phase current samples | Algorithm used | Combined DFT and fuzzy logic | Integrated moving sum approach | Wavelet transform and ChNN | Wavelet transform and fuzzy nuerosystem | Support vector machine | Number of test cases | 129600 | Not mentioned | 54000 | 23436 | 25200 | Fault resistance | 0.001 Ω–100 Ω | 10 Ω, 50 Ω, and 150 Ω | 0 Ω, 5 Ω, 25 Ω, and 50 Ω | 0.1 Ω, 5 Ω, 25 Ω, and 50 Ω | 0 Ω, 5 Ω, 25 Ω, and 50 Ω | Fault inception | 0°–360° | 54° and 90° | 0°, 45°, 80°, and 115° | 0°, 45°, and 90° | 0°, 45°, and 115° | Evolving fault considered | Yes | Not reported | Not reported | Not reported | Not reported | Compensation level | 10–65% | 70% | 25, 50, and 75% | 20, 40 and 60% | 25, 50 and 75% | Change in frequency | 58 Hz–62 Hz | Not reported | Not reported | Not reported | Not reported | Heavy load interconnection | Yes | Not reported | Not reported | Not reported | Not reported |
|
|