Research Article

Combined DFT and Fuzzy Based Faulty Phase Selection and Classification in a Series Compensated Transmission Line

Table 5

Effect of fault resistance (FIA = 45°).

Simulated system dataResults obtained from the proposed CDFTF-based scheme
Fault typeFL (km)FR (ohm)Response time (ms)Fault type
Phase APhase BPhase CGround G

ABG250.0013.7174.5174.517ABG
ABG55203.7174.5174.517ABG
ABG95804.5179.5175.417ABG
ABG175203.7179.5175.417ABG
ABG205404.18.35.8ABG
ABG2451006.2179.5177.017ABG