Combined DFT and Fuzzy Based Faulty Phase Selection and Classification in a Series Compensated Transmission Line
Table 7
Effect of fault type (FR = 50 Ω and FIA = 45°).
| Simulated system data | Results obtained from the proposed CDFTF-based scheme | Fault type | FL (km) | Response time (ms) | Fault type | Phase A | Phase B | Phase C | Ground G |
| AG | 50 | 3.30 | — | — | 2.50 | AG | BG | 160 | — | 8.717 | — | 4.517 | BG | CG | 250 | — | — | 7.017 | 6.217 | CG | ABG | 50 | 3.717 | 8.717 | — | 4.517 | ABG | BCG | 160 | — | 8.717 | 6.217 | 4.517 | BCG | CAG | 250 | 5.417 | — | 6.217 | 4.517 | CAG | AB | 50 | 3.717 | 11.217 | — | — | AB | BC | 160 | — | 7.917 | 7.917 | — | BC | CA | 135 | 6.217 | — | 6.217 | — | CA | ABC | 245 | 4.517 | 8.717 | 7.017 | — | ABC |
|
|