Research Article
Combined DFT and Fuzzy Based Faulty Phase Selection and Classification in a Series Compensated Transmission Line
Table 8
Simulation results for evolving faults.
| Simulated system data | Results obtained from the proposed CDFTF-based scheme | FT1 | FT2 | FR1 (Ω) | FR2 (Ω) | FL (km) | IT1 (s) | IT2 (s) | Time interval between IT1 and IT2 (ms) | Response time (ms) | Phase A | Phase B | Phase C | Ground G |
| AG | AG | 10 | 5 | 50 | 0.5000 | 0.5150 | 15 | 5.00 | — | — | 3.30 | AG | ABG | 10 | 20 | 100 | 0.5025 | 0.5125 | 10 | 4.10 | 6.60 | — | 2.50 | AG | ABCG | 20 | 50 | 160 | 0.5016 | 0.5276 | 26 | 5.00 | 8.20 | 5.70 | 3.40 | BG | BCG | 15 | 50 | 90 | 0.5100 | 0.5360 | 26 | — | 10.80 | 4.80 | 3.30 | BG | ABCG | 5 | 30 | 250 | 0.5158 | 0.5258 | 10 | 5.00 | 5.00 | 8.30 | 4.20 | AB | ABG | 50 | 50 | 10 | 0.5025 | 0.5105 | 8 | 4.10 | 10.80 | — | 4.50 | BC | ABC | 1 | 30 | 80 | 0.5058 | 0.5288 | 17 | 4.50 | 4.20 | 4.20 | — | BC | BCG | 30 | 50 | 200 | 0.5200 | 0.5370 | 17 | — | 6.60 | 6.60 | 3.80 | BC | ABC | 50 | 1 | 175 | 0.5016 | 0.5316 | 30 | 6.70 | 8.40 | 8.40 | — |
|
|
FT1, initial fault types; FT2, secondary fault types; FR1, initial fault resistance; FR2, secondary fault resistance; IT1, inception time for the initial fault type; IT2, inception time for the secondary fault type.
|