Research Article
Diagnosis and Classification Decision Analysis of Overheating Defects of Substation Equipment Based on Infrared Detection Technology
Table 1
Determination of relative temperature difference of current heating equipment.
| Type of equipment | Relative temperature difference fault range | General fault type | Major thermal failure | Emergency thermal failure |
| SF6 circuit breaker | ≥20% | ≥80% | ≥95% | Vacuum circuit breaker | ≥20% | ≥80% | ≥95% | Oil-filled casing | ≥20% | ≥80% | ≥95% | High-voltage switchgear | ≥35% | ≥80% | 95% | Isolating switch | ≥35% | ≥80% | ≥95% | Other conductive equipment | ≥35% | ≥80% | ≥95% |
|
|