Determination of relative temperature difference of current heating equipment.

Type of equipmentRelative temperature difference fault range
General fault typeMajor thermal failureEmergency thermal failure

SF6 circuit breaker≥20%≥80%≥95%
Vacuum circuit breaker≥20%≥80%≥95%
Oil-filled casing≥20%≥80%≥95%
High-voltage switchgear≥35%≥80%95%
Isolating switch≥35%≥80%≥95%
Other conductive equipment≥35%≥80%≥95%