Review Article

An Overview of Westinghouse Realistic Large Break LOCA Evaluation Model

Table 2

Sample results of various BELOCA analyses. (Comparison between the 1996 EM and 2004 ASTRUM EM)

Representative plant analysis1996 EM CQD2004 EM ASTRUM

2-loop with UPIPCT = 2087°F LMO < 17% CWO < 1%PCT = 1870°F LMO = 3.4% CWO 0.3% (18% Power Uprate)

3-loopPCT = 2050°F LMO = 12% CWO = 0.8%PCT = 1836°F LMO = 2.9% CWO = 0.03%

4-loopPCT = 2125°F LMO = 13% CWO = 0.9%PCT = 1967°F LMO = 2.4% CWO 0.4%