Separation of Transformers for Class 1E Systems in Nuclear Power Plants
Table 10
Variance in voltage during the plant start-up condition (Cat. I).
| Power source | 4.16 kV bus | Voltage regulation (%) | Was | Is | Variance (%) |
| UAT | Class 1E | 95.45 | 99.44 | 3.99 | Bus A | Class 1E | 95.53 | 99.51 | 3.98 | Bus B | Non-Class 1E | 99.53 | 99.51 | 3.98 | Bus A | Non-Class 1E | 95.45 | 100.07 | 4.62 | Bus B |
|
|