Separation of Transformers for Class 1E Systems in Nuclear Power Plants
Table 2
The result of short circuit current analysis for APR1400.
| Power source | 4.16 kV bus | Cat. I | Cat. II | Cat. III | Cat. IV | Cat. V |
| UAT | Non-Class 1E | 39.1 kA | 43.5 kA | 42.4 kA | 42.4 kA | 43.5 kA | Bus A | Non-Class 1E | 38.2 kA | 35.1 kA | 37.4 kA | 36.0 kA | 42.0 kA | Bus B | Class 1E | 35.1 kA | 32.2 kA | 34.7 kA | 33.3 kA | 43.0 kA | Bus A | Class 1E | 36.7 kA | 33.5 kA | 35.7 kA | 34.3 kA | 43.0 kA | Bus B |
| | Non-Class 1E | — | 42.7 kA | 42.4 kA | 42.4 kA | 42.6 kA | Bus A | Non-Class 1E | — | 35.4 kA | 37.9 kA | 37.4 kA | 42.7 kA | Bus B | Class 1E | — | 32.5 kA | 36.2 kA | 34.7 kA | 43.0 kA | Bus A | Class 1E | — | 33.8 kA | 35.0 kA | 35.7 kA | 43.0 kA | Bus B |
|
|
the plant start-up condition (Cat. I), the electric power system receives power only through UAT.
|