Development and Testing of TRACE/PARCS ECI Capability for Modelling CANDU Reactors with Reactor Regulating System Response
Table 3
Event timings compared to station data and previous studies.
| Event | Station data (s) | [18] (s) | This work (s) |
| Loss of class IV power | 0 | 0 | 0 | Turbine trip | 0 | 0 | 0 | Emergency stop valve (ESV) close | No data | 0.28 | 0.28 | Stepback on turbine trip | 0.5 | 0.5 | 0.5 | CSDV open | 0.8 | 0.8 | 0.8 | ASDV open | 1.0 | 13.6 | 13.5 | SDS1 low flow trip | 2.9 | 3.3 | 3.41 | Liquid relief valve (LRV) open | 3.5 | 4.2 | Not actuated | SDS2 low flow trip | 11.6 | N/A | N/A |
|
|
1This is the timing of when the trip condition is met—shutdown rod actuation is delayed by an additional 0.3 seconds.
|