Seismic Strengthening Effects Based on Pseudodynamic Testing of a Reinforced Concrete Building Retrofitted with a Wire-Woven Bulk Kagome Truss Damper
Table 5
Results of mechanical characterizations of test specimens following the cyclic loading test.
| Specimen | Load direction | Yield shear strength (kN) | Maximum shear strength (kN) | Displacement at the yield point (mm) | Displacement at the maximum point (mm) | Failure mode |
| CL-F | Positive | 468 | 530 | 12.5 | 25 | Flexural failure | Negative | −462 | −531 | −12.3 | −24.5 |
| CL-FK | Positive | 486 | 575 | 12.5 | 25.2 | Flexure | Negative | −485 | −570 | 12.1 | 24.3 |
|
|