Wind-Induced Coupling Vibration Effects of High-Voltage Transmission Tower-Line Systems
Table 11
Comparison of the displacements of the tower calculated by dynamic analysis in the tower-line system and the displacement given by the quasi-static calculations for the corresponding single tower.
Wind speed
Node number
Displacement in the -direction (m)
Displacement in the -direction (m)
TL
QS
TL/QS
TL
QS
TL/QS
m/s
727
0.091
0.071
1.28
−0.053
0.001
−53
660
0.070
0.055
1.27
−0.032
0.0002
−160
m/s
727
0.123
0.093
1.32
0.059
0.001
59
660
0.096
0.072
1.33
0.036
0.0004
90
m/s
727
0.145
0.105
1.38
0.080
0.001
80
660
0.112
0.081
1.38
0.050
0.001
50
m/s
727
0.170
0.117
1.45
0.102
0.001
102
660
0.133
0.091
1.46
−0.062
0.001
−62
m/s
727
0.202
0.131
1.54
−0.100
0.001
−100
660
0.157
0.102
1.54
−0.062
0.001
−62
m/s
727
0.192
0.145
1.32
0.116
0.001
116
660
0.150
0.113
1.33
0.070
0.001
70
m/s
727
0.221
0.160
1.38
0.096
0.002
48
660
0.172
0.124
1.39
0.061
0.001
61
m/s
727
0.258
0.175
1.47
−0.211
0.002
−105.5
660
0.201
0.136
1.48
−0.129
0.001
−129
m/s
727
0.286
0.186
1.54
−0.185
0.002
−92.5
660
0.223
0.144
1.55
−0.116
0.001
−116
m/s
727
0.301
0.202
1.49
−0.241
0.002
−120.5
660
0.235
0.157
1.50
−0.151
0.002
−75.5
m/s
727
0.426
0.225
1.89
−0.271
0.002
−135.5
660
0.334
0.175
1.91
−0.168
0.002
−84