Research Article

Experimental Evaluation for the Microvibration Performance of a Segmented PC Method Based High Technology Industrial Facility Using 1/2 Scale Test Models

Table 4

Comparison of natural frequency and response magnitude by the impact test on FAB floor.

ModeFrequency (Hz)Response (um/Ns)
Nonsegmented
Model
Segmented
Model
Ratio
(%)
Nonsegmented
Model
Segmented
Model
Ratio
(%)

1st16.215.294.013.17.154.2
2nd25.824.393.96.13.455.8
3rd33.330.491.55.24.178.9