Research Article
Shaking Table Array Tests of an Ultra-High-Voltage Cup-Type Transmission Tower-Line System
Table 8
Transverse peak displacement responses of the middle towers of the four models.
| Test series | Single-tower model (mm) | Single-tower model with suspended lumped masses (mm) | Three-tower-two-line model (mm) | Five-tower-four-line model (mm) |
| 0.07 g artificial wave | 2.134 | 1.687 | 3.126 | 1.848 | 0.07 g El Centro wave | 0.811 | 0.543 | 0.720 | 0.736 | 0.07 g Taft wave | 1.127 | 0.883 | 0.824 | 0.897 | 0.07 g average | 1.357 | 1.038 | 1.557 | 1.161 | 0.21 g artificial wave | 7.258 | 5.223 | 9.663 | 6.032 | 0.21 g El Centro wave | 2.148 | 2.447 | 2.514 | 2.089 | 0.21 g Taft wave | 3.962 | 2.233 | 2.976 | 3.130 | 0.21 g average | 4.456 | 3.301 | 5.051 | 3.750 | 0.63 g artificial wave | 21.152 | 16.141 | 26.785 | 16.364 | 0.63 g El Centro wave | 7.513 | 7.250 | 8.162 | 6.549 | 0.63 g Taft wave | 12.204 | 7.045 | 7.768 | 8.783 | 0.63 g average | 13.623 | 10.146 | 14.238 | 10.565 |
|
|