Research Article

Study on Seismic Reliability of UHVDC Transmission Systems

Table 2

Seismic reliability of important electrical equipment.

EquipmentExpectation (MPa)Variance (MPa)Reliability indexSeismic reliability (%)

Valve22.51.514.6899.99
Transformer21.35.52.9199.98
Reactor smoothing28.512.51.1988.30
Filter tower23.112.31.6094.52