Research Article

Research on Bending Rigidity at Flange Connections of UHV Composite Electrical Equipment

Table 9

Comparison of peak relative displacements of the top end of the bushing obtained by the test and simulation.

Artificial wave (g)TestModel-1Model-2

0.1187.9170.6171.0
0.2371.8341.2342.0
0.3532.2518.3520.0
0.4682.3713.8717.6