Research Article

Synthesis of Trigeneration Systems: Sensitivity Analyses and Resilience

Table 2

Results for optimal trigeneration system (base case) and conventional system.

System compositionConventional systemTrigeneration system
NumberTotal powerNumberTotal power

Gas engines 31739 kW
Hot water boilers 63420 kW31710 kW
Heat exchangers 41600 kW
Absorption chillers 1490 kW
Mechanical chillers 41960 kW31470 kW
Cooling towers 33000 kW33000 kW

Natural gas (total) MWh/yr870337,324
Purchased electricity MWh/yr357229
Sold electricity MWh/yr11,389
Natural gas (cogeneration) MWh/yr36,638
Cogenerated electricity MWh/yr14,954
Cogenerated useful heat MWh/yr8,602

Primary energy savings %10.01
Equivalent electrical efficiency %55.22

Annual fixed cost €/yr 219,650 510,830
Cost of natural gas €/yr217,582933,092
Cost of electricity €/yr366,9513207
Profit with the sale of electricity €/yr−876,960
Annual energy cost €/yr 584,534 59,339

Annual total cost €/yr804,184570,169