Research Article

Synthesis of Trigeneration Systems: Sensitivity Analyses and Resilience

Table 4

Sensitivity analysis for variations in energy demands considering the base case configuration.

Variation−20%−15%−10%−5%0%+5%

System composition
 Gas engines 333333
 Hot water boilers 333333
 Heat exchangers 444444
 Absorption chillers 111111
 Mechanical chillers 333333
 Cooling towers 333333

Natural gas (total) MWh/yr31,92133,52034,97636,40737,32437,389
Purchased electricity MWh/yr009162945
Sold electricity MWh/yr10,09010,52110,89211,24411,38911,188
Natural gas (cogeneration) MWh/yr31,75733,25634,58935,88036,63836,520
Cogenerated electricity MWh/yr12,96213,57414,11814,64514,95414,906
Cogenerated useful heat MWh/yr737177198028832886028857

Primary energy savings %9.779.779.779.7710.0110.70
Equivalent electrical efficiency %55.0055.0055.0055.0055.2255.87

Annual fixed cost €/yr510,830510,830510,830510,830510,830510,830
Cost of natural gas €/yr798,035838,003874,395910,169933,092934,714
Cost of electricity €/yr001076172032075083
Profit with the sale of electricity €/yr−776,967−810,149−838,713−865,824−876,960−861,441

Annual total cost €/yr531,899538,684547,588556,895570,169589,186