Research Article
The Effect Analysis of Strain Rate on Power Transmission Tower-Line System under Seismic Excitation
Table 4
Maximum base shear forces of 2nd transmission tower.
|
Seismic wave |
Peak acceleration (m/s2) | Shear force (kN) | X direction | Y direction | Without considering strain rate | Considering strain rate | Without considering strain rate | Considering strain rate |
| El Centro | 6.0 | 138.465 | 136.894 | 163.459 | 157.404 | 8.0 | 140.797 | 140.648 | 214.633 | 214.248 | 10.0 | 151.760 | 154.172 | 262.068 | 268.623 | 12.0 | 166.223 | 178.293 | 303.575 | 316.353 | 14.0 | 203.141 | 212.887 | 319.025 | 323.093 | 15.0 | Collapse | 222.141 | Collapse | 307.916 | 16.0 | Collapse | Collapse | Collapse | Collapse |
| Kobe | 6.0 | 198.513 | 198.516 | 228.912 | 228.911 | 8.0 | 228.882 | 228.878 | 260.429 | 260.427 | 10.0 | 279.233 | 281.514 | 283.561 | 285.820 | 12.0 | 248.166 | 252.340 | 263.036 | 267.653 | 13.0 | 279.085 | 291.489 | 256.623 | 259.124 | 14.0 | Collapse | 301.570 | Collapse | 267.427 | 15.0 | Collapse | Collapse | Collapse | Collapse |
| Northbridge | 10.0 | 247.764 | 248.244 | 216.227 | 216.941 | 15.0 | 289.418 | 289.030 | 309.638 | 309.181 | 20.0 | 393.213 | 396.100 | 453.791 | 453.690 | 23.0 | 456.353 | 458.828 | 469.431 | 474.372 | 25.0 | 467.501 | 474.122 | 464.471 | 473.617 | 27.0 | 465.700 | 481.191 | 500.019 | 520.178 | 29.0 | Collapse | 485.623 | Collapse | 523.600 | 30.0 | Collapse | Collapse | Collapse | Collapse |
|
|