Lanchow 330 kV substation noise control plan.
| Items | Constitution | Sound power level before noise reduction | Sound power level after noise reduction | Service condition |
| Plan A | Firewalls | Transformer 99 dBA Reactor 85 dBA | Transformer 99 dBA Reactor 85 dBA | Conventional design | Plan B | Plan A + reactor Box-in technique | Transformer 99 dBA Reactor 85 dBA | Transformer 99 dBA Reactor 70 dBA | HVDC station and substation have begun to practice | Plan C | Plan A + transformer Box-in technique | Transformer 99 dBA Reactor 85 dBA | Transformer 84 dBA Reactor 85 dBA | HVDC station has begun to practice, substation has not been applied | Plan D | Plan B + transformer Box-in technique | Transformer 99 dBA Reactor 85 dBA | Transformer 84 dBA Reactor 70 dBA | HVDC station has begun to practice, substation has not been applied |
|
|
HVDC station: high voltage direct current transmission substation.
|