Research Article
A Novel Multiobjective Control of DVR to Enhance Power Quality of Sensitive Load
Table 2
Voltage sag compensation of three-phase balanced fault.
| Tuning method/parameter 2 | Voltage at PCC in pu | Voltage at sensitive load in pu (compensated) | Phase A | Phase B | Phase C | Detroit Edison sag score (SS) | Phase A | Phase B | Phase C | Detroit Edison sag score (SS) |
| ZN | 0.4944 | 0.4884 | 0.4884 | 0.5096 | 1.007 | 1.006 | 1.006 | 0.006633 | SPSO | 0.4943 | 0.4882 | 0.4883 | 0.5097 | 1.001 | 0.9996 | 0.9993 | 0.000033 | AGPSO1 | 0.4946 | 0.4889 | 0.4890 | 0.5091 | 0.9997 | 0.9999 | 1.000 | 0.000133 | AGPSO2 | 0.4938 | 0.4876 | 0.4882 | 0.5101 | 1.000 | 1.000 | 0.9999 | 0.000033 | AGPSO3 | 0.4943 | 0.4881 | 0.4889 | 0.5095 | 0.9996 | 1.000 | 0.9999 | 0.000166 |
|
|