Summary of design specifications for the test system.
| Parameters description | Values with units |
| Source voltage/frequency | 22.5 (kV)/(50 Hz) |
| Load A parameters | Configuration: grounded Nominal phase-to-phase voltage (): 415 V Nominal frequency: 50 Hz Active power: 2500 W Inductive reactive power: 400 (positive var) |
| Load B parameters | Configuration: grounded Nominal phase-to-phase voltage (): 415 V Nominal frequency: 50 Hz Active power: 2500 W Inductive reactive power: 40 (positivevar) Capacitive reactive power: 10 (negative var) |
| Distribution transformer | Nominal power: 32 (kVA) Winding 1 parameters: 22500 V/star configuration, = 0.0003 (pu) = 0.001 (pu) Winding 2 parameters: 415 V/star configuration, = 0.0003 (pu) = 0.001 (pu) Magnetization resistance () and magnetization inductance () = 500 (pu) |
| Series injection transformer | Rated power: 5 kVA/50 Hz Winding 1 parameters: 100 V, = 0.00001 (pu) = 0.0003 (pu) Winding 2 parameters: 1000 V, = 0.00001 (pu) = 0.0003 (pu) Magnetizing branch: , = 500 (pu) |
| PWM generator | Switching frequency = 10 kHz |
| DC voltage source | 200 V |
| Passive filter | Series filter impedance: = 0.2 Ω, = 6 mH Shunt filter impedance: = 0.2 Ω, = 20 µ F |
|
|