Abstract

The polymer cutoff wall offers the benefits of causing little disturbance to the dam body, being convenient and economical to construct and practical to use, and possessing good resistance to seismic shocks and cracks. It has been widely used to prevent seepage and to reinforce dikes and dams. However, the polymer cutoff wall is a concealed underground structure, and nondestructive testing methods to ensure its integrity are not yet mature. This paper describes a modal analysis of polymer cutoff wall models with different damage scenarios to investigate the feasibility of nondestructive testing of the polymer cutoff wall based on vibration theory. The dynamic characteristics of the first three natural frequencies of the wall and their mode shapes show that horizontal direction damage and centrally located partial damage have a noticeable impact on the dynamic characteristics of the wall, indicating that nondestructive testing based on vibration theory is useful to test for horizontal damage and moderate damage located centrally in the wall.

1. Introduction

China has built about 98,000 reservoirs: about 4700 large and medium-sized reservoirs and more than 94,000 small reservoirs. The total length of the embankments is over 410,000 km. Most of this water conservancy infrastructure was built between 1950 and 1970. Some embankments had inherent defects due to the low level of available technology and economic austerity in that period. Long-term disrepair, flooding, earthquakes, and other natural disasters have made these reservoirs sources of disease. Any reservoir accident is likely to severely affect human security, leading to immeasurable loss of life and property damage [1, 2].

Nonaqueous reaction polymer grouting is a new antiseepage technology that has been developed to reinforce soil dikes and dams to prevent seepage [3]. It is a product of the National Water Conservancy Advanced Practical Technology Key Promotion project. This technology adopts the construction technique of static pressure groove formation, lifting grouting, and sleeve hole connections to realize the simultaneous construction of pressure groove grouting. Polymer cutoff walls provide many significant advantages over cement or concrete cutoff walls [4]: they can be rapidly and accurately constructed, there is little disturbance to the dam when they are installed, they are economical and practical in use, and they have good resistance to seismic activity, cracking, and corrosion [5].

The integrity of a polymer cutoff wall is important for the safe operation of the dam. The polymer cutoff wall is underground and therefore concealed. Thus, nondestructive testing of the polymer cutoff wall is a necessity. However, current research on polymer cutoff walls is mainly concerned with their static and dynamic properties [69], and there are few studies of nondestructive testing methods for polymer cutoff walls [10]. One nondestructive testing method, which is based on vibration theory, assesses the integrity of a cutoff wall by determining changes in modal or structural parameters [11]. This method provides the benefits of maintaining structural integrity, rapid damage detection, and low cost and can be used for large-scale inspections. However, the applicability of nondestructive testing methods based on vibration theory to thin and lightweight polymer cutoff walls has not been conclusively demonstrated [12].

Nondestructive testing based on vibration theory is a global method that requires the measurement of modal parameters of the system under investigation, such as natural frequency and mode shape. The underlying paradigm is that modal parameters of a system are a function of the physical properties of the system (such as stiffness, mass, and damping), so changes in the physical properties of the structure will lead to corresponding changes in the modal parameters of the structure [13]. Conversely, changes in modal parameters can also indicate changes in physical structural properties [14]. Lifshite and Rotem initially proposed that structural damage could be detected by observing changes in the natural frequency of the structure [15]. The method they introduced has been widely used for large civil engineering structures in fields such as aviation, aerospace, and precision machinery and for oil drilling platforms, large bridges, super-high-rise buildings, and large span grids [16]. Li analyzed the parameters and modeled the dynamics of vibrations in a damaged bridge structure in multiple steps. The author first created a model of the entire bridge and identified the approximate location of the structural damage and then quantified the extent of the damage. The study accurately identified and quantified the damage [17]. Liu and He demonstrated the feasibility and effectiveness of the use of the frequency ratio of a structure as a diagnostic index of structural damage through experimental tests of straight steel pipes, steel shells, and a 5-story steel frame structure [18]. Cheng et al. investigated the sensitivity to structural damage of several mode indicators of typical gravity dams through numerical modeling and physical experiments. They found that, of the parameters they investigated, COMAC and the Lipschitz index were the most sensitive to structural damage [19].

In this paper, we propose a modal analysis of various states of polymer cutoff walls: intact, horizontally damaged, vertically damaged, and partially centrally damaged. We compare the first three natural frequencies and modes of each damaged cutoff wall with those of the intact cutoff wall. Our investigation of the applicability of nondestructive testing methods based on vibration theory for the polymer cutoff wall will provide a theoretical basis for future nondestructive testing of polymer cutoff walls.

The principle of nondestructive frequency testing is to apply a certain level of excitation to cause the structure to vibrate and then to instrumentally measure the excitation force and the responses of the structure, such as displacement, velocity, and acceleration. The modal characteristics of the structure are then obtained by digital signal processing techniques, and the damage is then determined according to changes in the modal parameters of the structure. Thus, nondestructive testing enables us to observe changes in the modal parameters of the polymer cutoff wall to determine whether it is damaged. The quality and stiffness of the damaged polymer cutoff wall will change its natural frequency, and this change will be observed in the detection of vibration and the vibration mode. Thus, it is necessary to investigate vibration mode changes between the intact and damaged polymer cutoff walls.

2.1. Calculation Model

Each section of the polymer cutoff wall of the subject dam was 10 m long, its width was 0.03 m, and its depth was 15 m. The polymer material used in the wall had density ρ = 240 kg/m3, elastic modulus E = 180 MPa, and Poisson ratio μ = 0.20. The polymer cutoff wall was modeled by SOLID 185 element. The soil density of the dam was ρ = 1740 kg⁄m3, the shear wave (transverse wave) velocity was  = 241 m/s, and the compression wave (horizontal wave) velocity was  = 439 m/s, determined by on-site wave velocity measurement.

There is interaction between a polymer cutoff wall and the surrounding soil, so the influence of the surrounding soil on the polymer cutoff wall should be considered when modal analysis is undertaken to calculate the dynamic characteristics of the polymer cutoff wall. The effects of the soil on the polymer cutoff wall can be modeled by equivalent stiffness springs. In this paper, COMBIN 14 element is selected for the establishment of spring unit. Equivalent stiffness is determined by extension of the equivalent stiffness of the pile foundation. The equivalent stiffness [11] iswhere is the dynamic shear modulus of the surrounding soil, is the Poisson ratio of the surrounding soil, is the side area of the polymer cutoff wall, is the bottom area of the polymer cutoff wall, and L is the perimeter of the bottom of the polymer cutoff wall.

The parameters , , and L are determined by the actual size of the polymer cutoff wall. and are determined by the following equations [20]:where ρ is the density of the soil medium around the polymer cutoff wall, is the shear wave velocity of the soil medium around the polymer cutoff wall, and is the compression wave velocity of the soil medium around the polymer cutoff wall.

The polymer cutoff wall sections were connected to each other relatively firmly using sleeve connections. The boundaries between polymer cutoff walls were, therefore, considered to be fixed. The two sides of the polymer cutoff wall were in contact with the soil, were considered to be infinite, and were perpendicular to the direction of vibration excitation. It was, therefore, assumed that the cutoff wall was not displaced in this direction. The natural frequency of higher order vibrations is short, the natural vibration period is low, and any impact on the structure was difficult to observe [21]. Thus, in the modal analysis of the polymer cutoff wall, only the first three natural frequencies and natural vibration modes of the polymer cutoff wall were considered.

In modeling damage on the polymer cutoff wall, three different damage scenarios were considered: in the horizontal direction, in the vertical direction, and in the central part of the wall. For each type of damage, we considered both mild and moderate damage. The horizontal length of the intact polymer cutoff wall was , its vertical height was , and the length and height of the damage to the wall were, respectively, and .

2.2. Calculation Results
2.2.1. Intact Polymer Cutoff Wall

The intact polymer cutoff wall model consisted of 287,200 units and 96,907 nodes. Equation (1) gives the equivalent stiffness of the soil surrounding the intact impermeable wall as K = 4.1732 GN/m. Modal analysis calculated the first 3 natural frequencies of the intact polymer cutoff wall, which are shown in Table 1. The shapes of the first three modes are shown in Figure 1.

2.2.2. Horizontal Damage to Polymer Cutoff Wall

For slight damage to the polymer cutoff wall in a horizontal direction, we supposed that the polymer cutoff wall had separated at a distance of 1 m from the boundary. In this scenario, the horizontal length of the polymer cutoff wall  = 9 m. There were 254 710 units and 85 705 nodes in the model. Equation (1) gave an equivalent stiffness of the soil surrounding the intact impermeable polymer wall as K = 4.10303 GN/m. For moderate damage to the wall, we supposed that it had separated at a distance of  m from the boundary and that the length of the damaged polymer cutoff wall  = 7.5 m. There were 206 381 units and 69 549 nodes in the model. Equation (1) gave an equivalent stiffness of the soil surrounding the intact impermeable polymer wall as K = 4.1003 GN/m. Because the entire wall was broken, the fracture surface was no longer constrained by adjacent wall sections. In the two horizontal damage cases, modal analysis gave the first three natural frequencies of the horizontally damaged polymer cutoff wall that are shown in Table 2; the first three natural frequency modes are shown in Figure 2 and Figure 3.

2.2.3. Vertical Damage to Polymer Cutoff Wall

For slight damage to the polymer cutoff wall in the vertical direction, we supposed that the wall had separated vertically for a distance of 1 m starting at the bottom of the wall and that the height of the wall was  = 14 m. There were 270 404 units and 90 874 nodes in the model. Equation (1) gave the equivalent stiffness of the soil surrounding the intact impermeable wall as K = 3.8319 GN/m. For moderate damage to the wall, we supposed the wall had separated at the bottom for a height . The height of the wall was  = 12.25 m. There were 284 847 units and 72 542 nodes in the model. Equation (1) calculated the equivalent stiffness of the soil surrounding the wall as K = 3.0825 GN/m. Modal analysis of these two scenarios showed the first three natural frequencies of the polymer cutoff wall with vertical damage to those shown in Table 3. The first three-mode shapes are shown in Figures 4 and 5.

2.2.4. Partially Centrally Damaged Polymer Cutoff Wall

For partial damage at the center of the polymer cutoff wall, we supposed that a circular area of soil with a diameter of 1m was incorporated in an area at the center of the wall. The polymer material in this area was replaced by the surrounding soil. There were 298 242 units and 98 418 nodes in this model. Equation (1) calculated the equivalent stiffness of the soil surrounding the wall as K = 4.1044 GN/m. For moderate damage to the wall, we supposed there was a circular area of soil with a diameter of m in the center of the wall. There were 215 500 units and 94 259 nodes in the model. Equation (1) calculated the equivalent stiffness of the soil surrounding the wall as K = 4.1044 GN/m. Modal analysis showed that the first three natural frequencies of the partially damaged wall are those shown in Table 4. The first three-mode shapes are shown in Figures 6 and 7.

3. Analysis of Dynamic Characteristics

Table 2 shows that, for the polymer cutoff wall that was damaged horizontally, the first three natural frequencies differed greatly from those for the intact wall. In the case of mild damage, the first three natural frequencies decreased, respectively, by 38%, 44%, and 40%. In the case of moderate damage, the respective decreases were 30%, 44%, and 40%. A comparison of Figures 2 and 3 with Figure 1 clearly shows that there was a great change in the horizontally damaged wall. Therefore, any one of the first three modes can be used to determine the integrity of a polymer cutoff wall with damage in the horizontal direction.

Table 3 shows that the first three natural frequencies of the polymer cutoff wall were within a small range. In the case of mild damage, the first three natural frequencies increased, respectively, by 1%, 0%, and 0%. In the case of moderate damage, the first three natural frequencies increased, respectively, by 7%, 0%, and 3%. A comparison of Figures 4 and 5 with Figure 1 shows that the polymer cutoff wall with damage in the vertical direction was similar in terms of frequency to the three-mode diagram of the intact wall, which makes the damaged wall almost indistinguishable from the intact wall. Thus, this method is not sensitive to vertical damage to the polymer cutoff wall and is therefore not suitable for indicating the integrity of the wall.

Table 4 shows that, in the case of minor local damage to the center of the wall, the first three natural frequencies of the polymer cutoff wall decreased, respectively, by 3%, 5%, and 0%. In the case of moderate local damage, the first three natural frequencies decreased, respectively, by 17%, 29%, and 10%. Thus, any one of the first three modes can be used to indicate the integrity of the partially damaged polymer cutoff wall when the damage is large.

4. Conclusion

In this paper, through modal analysis of the polymer cutoff wall, using the intact, horizontally damaged, vertically damaged, and partly centrally damaged polymer cutoff wall as the basic models, the first three natural frequencies and natural modes of the three models were analyzed and compared with the model of the intact wall. The vibration shape shows that nondestructive testing methods based on vibration theory can be used to indicate the integrity of polymer cutoff walls, but they are individually sensitive to different types of damage.(1)When the polymer cutoff wall was horizontally damaged, the images of the first three natural frequencies and modes of the damaged polymer cutoff wall were quite different from those of the intact polymer cutoff wall. Any of the first three modes will indicate the integrity of the wall.(2)When the polymer cutoff wall was vertically damaged, the first three natural frequencies and the three-mode diagrams of the damaged polymer cutoff wall do not change significantly from those of the intact wall, and the sensitivity to this condition is not high.(3)When the polymer cutoff wall is damaged in the center, the first three natural frequencies of the damaged polymer cutoff wall and the range of the three modes will increase as the damage increases. The sensitivity of this method also increases as the degree of damage increases.

Data Availability

The data used to support the findings of the study are available from the corresponding author upon request.

Conflicts of Interest

The authors declare that they have no conflicts of interest.

Acknowledgments

This work was supported by the National Key Research and Development Program of China (Grant no. 2017YFC1501204), the Natural Science Foundation of Henan Province (Grant no. 212300410279), and the Open Research Fund of Water Engineering Materials and Structures, Guangxi Institute of Water Resources Research (Grant no. GXHRI-WEMS-2020-04). The authors would like to thank for these financial supports.