Abstract

Cracks will be generated due to high internal temperature of the massive concrete. Postcooling method is widely employed as a standard cooling technique to decrease the temperature of the poured mass concrete. In this paper, an annular finned cooling pipe which can increase the heat transfer area between the flowing water and its surrounding concrete is proposed to enhance the cooling effect of the postcooling method. Analysis of the interior temperature variation and distribution of the concrete block cooled by the annular finned cooling pipe system and the traditional cooling pipe system was conducted through the finite element models. It is found that, for the concrete block using the proposed annular finned cooling pipe system, the peak value of the interior temperature can be further lowered. Compared with the traditional cooling pipe, the highest temperature of concrete with an annular finned cooling pipe appears earlier than that with the traditional cooling pipe.

1. Introduction

In the construction of dams and long-span suspension bridges, mass concrete blocks are cast. The released hydration heat of the massive concrete cannot be dissipated quickly because of the poor thermal conductivity of concrete. Therefore, a large temperature difference can be generated between the surface and the core area of the concrete during the early stage of the pouring concrete [13]. The large temperature difference may lead to cracks, which may reduce the durability of the massive concrete [46]. Therefore, reducing the internal temperature of massive concrete becomes a research hotspot during the past few decades.

An efficiency way named postcooling method is often used to change the internal temperature distribution of the massive concrete structures [7, 8]. The internal temperature distribution of mass concrete can be changed by the cool water running through pipes. The cooling effect of the postcooling method has been verified during the construction process of Hoover dam in the last century [9]. After that, loads of scholars have emerged in this research area. The content of the research mainly embraces three aspects: theoretical model, numerical simulation, and practical test.

In terms of theoretical model: Zhu and Cai [10] investigated the cooling efficiency of the pipe during the construction of the pouring concrete. A theoretical method was given for analyzing the heat transfer between the concrete and the cooling fluid. Meanwhile, some practical computing methods and relevant charts were presented for the convenience of engineers. Feedback analysis method for calculating the temperature variation in mass concrete structures was presented by Ding and Chen [11]. The method was applied in a dam during its construction period. Zhong et al. [12] put forward a composite element method to improve the computational efficiency in the calculation of temperature distribution in mass concrete with water running in the cooling pipe. The availability of the proposed method was confirmed by finite element method. The theoretical solution of nonmetallic cooling pipe, compared with metallic cooling pipes, was investigated by Chen et al. [13]. Mogharrebi et al. [14] proposed an evaluation of 3D convective heat exchange characteristics of magneto-hydrodynamic nanofluid flow, containing motile oxytactic microorganisms and nanoparticles passing through rotating cones.

In terms of numerical simulation, Kim et al. [15] investigated the hydration heat of the mass concrete embedded with cooling water pipeline by using a finite element program. By comparing to the data measured from the process of the construction of a bridge in Korea, the simulation results obtained through the three-dimensional finite element program showed good agreements. Myers et al. [16] proposed an approximate model for simulating the cooling process of the massive concrete with cooling pipe. An analytical model was also presented for simulating the heat generation process of the concrete. Yang et al. [17] proposed a finite element program for analyzing the thermal distribution of the massive concrete. Through the experimental verification, it is certificated that the numerical model is effective in calculating the temperature distribution of mass concrete. For reflecting the temperature distribution around the cooling pipe, a procedure for a heat-fluid coupling model was putted forward by Liu et al. [18]. Hong et al. [19] put forward a numerical simulation algorithm of transient temperature field considering the influence of ambient temperature and cooling pipe size. Rostami et al. [20] numerically simulated the convective heat exchange under the effect of magnetic forces in Al2O3-rthylene glycol nanofluids in porous media. Boussinesq-Darcy law and thermal nonequilibrium model are adopted. The suspension of phase change material was employed as a new fluid material by Qian and Guo [21] to assess its cooling performance. The simulation results present that the highest temperature of concrete can be significantly decreased by replacing water with suspension of phase change substances.

In terms of practical test, Liu et al. [22] developed a heat-fluid coupling way to conduct the heat simulation of a cooling pipe system. Corresponding tests were conducted to certificate the availability of the proposed heat-fluid coupling method. Based on a scaled experimental model, the temperature distribution and temperature time histories for the core area of the concrete were monitored by Huang et al. [23]. The test results show that the pipe cooling system can greatly reduce the temperature rise. Wu et al. [24] investigated the influence of sodium hydroxide on the hydration of low carbon cementing materials. Geng et al. [25] employed the air pipe cooling technique to transform the temperature distribution of concrete walls; an experimental study of a large dimension wall with properly embedded corrugated pipes was conducted. Hong et al. [26] put forward a collocation method using the localized radial basis function to calculate the temperature distribution in concrete structures with cold pipe. Examples including a problem with multicooling water pipes were investigated. From the calculation results, it can be known that the method can be used in the calculation of temperature distribution in mass concrete structures embedded with cooling pipe systems. Hybrid nanofluid flow containing MoS2–TiO2 hybrid nanoparticles under the effect of the magnetic field in cavity enclosure has been evaluated by Hosseinzadeh et al. [27]. It was found that the position of horizontal ellipse provides better conditions for fluid flow and thermal convection.

It is widely known that the cooling effect of the postcooling method is limited by the superficial area of the traditional cooling pipe system. Therefore, the one-time pouring height of the massive concrete is usually less than 3 m. Thus, a new cooling pipe system which can increase the cooling efficiency of the massive concrete is needed during the construction of the structures. According to the laws of thermodynamics, the heat transfer efficiency can be increased by increasing the heat exchange area. Therefore, an annular finned cooling pipe which can increase the heat transfer area between the flowing water and its surrounding concrete is proposed in the paper to decrease the internal temperature of the concrete block. Internal temperature variation and distribution of the concrete block is calculated to study the cooling influence of the proposed annular finned cooling pipe.

2. Description and Validation of the Numerical Model

2.1. Numerical Model and Its Governing Equations

A commercial software Ansys V 17.0 is used to calculate the hydration heat of massive concrete with cooling pipe. The unsteady conductivity is calculated by the finite volume method, and its control formula is as follows:where , , , , and are density, thermal conductivity, temperature, hydration heat per unit of volume, and the specific heat, respectively.

The equation used for the whole hydration heat of the used materials iswhere Q0 is the whole hydration heat of the cement. k1 and k2 are the hydration heat adjustment coefficients of cement, mixed with slag and fly ash.

The following is the formula of the thermal insulation warming:where W represents the consumption of P·I Portland cement in per cubic meter of concrete; t is the age of concrete; W0 represents the amount of other types of Portland cement and is the correction coefficient; C stands for the concrete specific heat capacity; is the concrete density; m is the cementitious coefficient related to the properties of cement, and the formula iswhere A and B represent concrete casting temperature correlation coefficients.

The water flow in the pipeline is simulated through the standard model. The rate of dissipation and the turbulence kinetic energy are used in the model as follows:

Here, , , and are constants; stands for the turbulence kinetic energy created by buoyancy; stands for the contribution of fluctuating dilatation to the total dissipation rate in compressible turbulence. and are the number of turbulent planters of and , respectively. represents the turbulence kinetic energy due to the average velocity gradient; and and are user-defined sources.

2.2. Validation of the Numerical Model

For verifying the correctness of the numerical model, as shown in Figure 1, we compare the interior temperature of cylindrical concrete obtained from the numerical model ground on the control formula described in Section 2.1 with the theoretical value. The cylindrical concrete has a radius of 0.4225 m and a length of 2.0 m. Cooling water flows through a cylindrical axial pipe. The outer radius of the tube is 0.008 m, and the inner radius is 0.007 m. The concrete pouring temperature is 273 K, and the water inlet temperature is 273 K. P·O 42.5 Portland cement with hydration heat as Figure 2 shows is employed. The proportion of the concrete is depicted in Table 1. On the basis of the standard for construction of mass concrete of China MOHURD [28], the parameters which are needed to identify equation (3) are listed in Table 2. Combining Figure 2 and Tables 1 and 2, the thermal insulation warming of concrete can be expressed as

A theoretical solution which was proposed by Zhu [29, 30] is employed here to verify the accuracy of the numerical model. For a steel cooling pipe with outer radius c and inner radius r0 embedded in a cylindrical concrete (in Figure 1(b)), the heat conduction equation in the cylindrical concrete can be shown as

The boundary conditions of the cylindrical concrete are

The solution of equation (9) can be obtained by the Laplace transformation method, and it can be expressed aswhere is the root of the following equation:where Y0 and Y1 are the zero and first order of Bessel functions of second kind, respectively, and J0 and J1 are the zero and first order of Bessel functions of first kind, respectively.

Through equation (11), the mean temperature of plane A in Figure 1(a) can be calculated by

The average temperature of plane A obtained by numerical model calculation is compared with the result calculated by equation (13), as shown in Figure 3. The research indicates that the average temperature of plane A obtained through the numeral model is basically consistent with the theoretical results. Therefore, the interior temperature of concrete blocks with cooling pipes can be simulated by using the numeral model based on control formula described in Section 2.1.

3. Interior Temperature Distribution of Massive Concrete

3.1. Parameters Setting of the Numerical Model

Three typical finite element models with the same geometric size of the concrete as shown in Figure 4 are employed to study the internal temperature distribution of mass concrete. Figure 5 shows the schematic of the interchange of heat between the annular finned cooling pipe and the concrete. Through Figure 5, it can be directly known that the surrounding annular fins of the cooling pipe play two roles: firstly, they can increase the heat transfer area between the core area of the concrete and the flowing water; secondly, as the annular fins are always metal, the heat conductivity coefficient is larger than that of concrete; therefore, the annular fins apply a fast heat exchange path.

As shown in Figures 4 and 5, the surface is mounted with fin rows with height hp, spacing , and thickness . The outer diameter of the cooling pipe is D. represents the thickness of the cooling tube. The length of the cooling pipe is lp, and the length of the circumferential fins from the first piece to the last piece is lf. O denotes the geometric center of the concrete block at (0.0, 0.0, 0.0). dc, hc, and lc shown in Figure 4 stand for the geometric dimensions of large-capacity concrete in x, y, and z directions, respectively.

Tetrahedral elements are used to form concrete, pipes, and water flows in pipes, as shown in Figure 6(a). The highest expansion layer number of water near the pipeline is 3, and the expansion increase rate is 1.2, as shown in Figure 6(b). The average element mass of tetrahedral elements is above 0.8, and the deviation value of tetrahedral elements is about 0.2.

Thermal and geometric properties of the concrete and the pipe are given in Table 3. In Table 3, CP means the traditional cooling pipe, and AFCP stands for the annular finned cooling pipe. The velocity of inlet water is 0.6 m/s, the water influent temperature is 298 K, and the ambient temperature is 303 K. The heat transmission between the surrounding environment and the concrete surface is simulated through the terminal condition of heat convection, and the surface heat transmission coefficient is 3.6 W/m2K.

3.2. Numerical Results

In this section, the interior temperature distributions of the concrete without cooling pipe, the concrete with traditional cooling pipe, and the concrete with annular finned cooling pipe are investigated. The cooling effect of the concrete with the traditional and the annular finned cooling pile is compared through plane A1 in Figure 7(a). Calculation results of the temperature distribution nephogram of plane A1 for t = 1.5 days, 2.5 days, and 3.5 days are presented in Figure 8. Through Figure 8, it can be obtained that high temperature gradient between the core area and the surface area is generated for the concrete without the cooling pipe. For the concrete with the traditional pipe and the annular finned pipe, the value of the temperature of the core area reduced. Meanwhile, comparing Figures 8(b) and 8(c), the cooling region of the concrete embedded with the annular finned cooling pipe is larger than that with the traditional cooling pipe. Therefore, a conclusion that annular finned cooling pipe system has a better cooling efficiency than the traditional cooling pipe system can be obtained.

In order to record the temperature history of the interior area of the concrete, four points are selected in Figure 7(b). The coordinates of points a, b, c, and d are (0.1 m, 0.1 m, 0.0 m), (0.2 m, 0.2 m, 0.0 m), (0.3 m, 0.3 m, 0.0 m), and (0.4 m, 0.4 m, 0.0 m), respectively. Temperature histories of the selected points are exhibited in Figure 9. It can be obtained from Figure 9 that the highest temperature of concrete blocks cooled by traditional cold pipe method or annular finned cold pipe method is obviously reduced. At point a, the peak temperatures of concrete without CP, concrete containing CP, and concrete containing AFCP are 337 K, 322 K, and 309 K, respectively. The decrease degree of concrete peak temperature with annular finned cooling pipe is greater than that with traditional cooling pipe. The occurrence time of the maximum temperature of concrete with cooling pipe is shorter than that of concrete without cooling pipes. Meanwhile, the concrete with annular finned cooling pipe reaches the maximum temperature earlier than the traditional cooling pipe. At point a, the peak temperature of CP-free concrete, CP-containing concrete, and AFCP-containing concrete appeared for 2.0 days, 1.5 days, and 1.0 day, respectively. The above phenomenon is more obvious in approaching the cooling pipe system. Because points c and d are far away from the cooling pipe system, the internal temperature decreases less than points a and b. The temperature drop of point d concrete far away from the core area of concrete is mainly due to atmospheric transmission between the surface of mass concrete and the ambient environment.

Three sections as exhibited in Figure 10 are chosen to draw the temperature distribution of concrete depth. Temperature distribution through the depth at selected sections B, C, and D are shown in Figure 11. It can be known that the temperature distribution at each section is reduced for the concrete with the cold pipe system. The temperature loss degree at section B is more obvious than that at sections C and D due to a reason that section B is closer to the cooling pipe. In addition, for concrete with annular finned cooling pipes, it can also be concluded that the cooling efficiency of internal temperature is higher than that of concrete with traditional cooling pipes.

3.3. Investigation of the Cooling Efficiency of the Annular Finned Cooling Pipe

As mentioned previously, the main property of the annular finned cooling pipe is that the heat exchange area increases compared to the traditional cooling pipe. Therefore, in this section the cooling efficiency of the annular finned cooling pipe with variation of the heat exchange area is discussed. As can be seen in Figure 5, keeping lf as a constant but varying the distance , the heat exchange area also changes. Thus, three conditions with  = 100 mm, 200 mm, and 400 mm are investigated. The calculated temperature of the selected points a, b, c, and d is shown in Figure 12. It can be known from Figure 12 that, with decrease of the value of (which means the value of the heat transfer area increases), the cooling performance of the annular finned cooling pipe increases. Therefore, it is concluded that the surface area of the annular finned cooling pipe can dominate the internal temperature distribution of the concrete if the other parameters of the pipe are the same.

Table 4 depicts three calculation conditions. They have a common point that all the employed annular fined cooling pipes have the same heat exchange surface. Calculated temperatures of the points a, b, c, and d are shown in Figure 13. A very interesting phenomenon can be obtained that, for the points b, c, and d which are a little far from the pipe, the temperature histories are almost identical with each other. However, for point a, the temperature histories of AF_200_100, AF_100_66.4, and AF_400_143.6 have obvious differences. The reason is that, for the point a, which is near the cooling pipe, the temperature of the point is not only dominated by the surfaces area of the annular finned cooling pipe, but also controlled by the distance between the point and the adjacent annular fins. For the mental annular fins, they have a higher heat conductivity coefficient than the concrete; thus the points which are adjacent to the annular fins have shorter heat transfer path. Calculation results of the temperature distribution nephogram of plane A1 for 2.5 days are shown in Figure 14. Through Figure 14, it can be obtained that, for the area near to the cooling pipe, the temperature distributions of AF_200_100, AF_100_66.4, and AF_400_143.6 have some differences. Moreover, for the area a little far from the pipe, the temperature distribution is almost the same. Therefore, what we can say is that the surface area and the distance between the point and the annular fins are the two key factors which control the temperature distribution of the concrete.

4. Conclusions

A novel annular fin cooling pipe for reducing the internal temperature of mass concrete is proposed. A 3D finite element model is employed to study the temperature distribution of massive concrete cooling pipes with annular finned and traditional cooling pipes. The results lead to the following conclusions:(1)Concrete with traditional cooling pipes or annular finned cooling pipes can reduce the temperature in the core area. However, compared with traditional cooling pipes, the cooling range of annular finned cooling tubes is wider. Thus, the annular finned cooling pipe system has a better cooling efficiency than the traditional cooling pipe system.(2)For concrete embedded with traditional cooling pipes or annular finned cooling pipes, the peak temperature can be reduced. However, comparing the traditional cooling pipe, the peak temperature of concrete in the annular finned cooling pipe decreases more. The concrete with annular finned cooling pipe has the highest temperature earlier than the traditional cooling pipe.(3)At points near the cooling pipe system, the temperature drops more than at points away from the cooling pipe system. Under the condition of constant inlet velocity and inlet temperature, the surface area of the cooling pipe and the distance between the cooling pipe and the annular finned are two important factors to control the temperature distribution of concrete.