Overvoltage and Insulation Coordination of Overhead Lines in Multiple-Terminal MMC-HVDC Link for Wind Power Delivery
Table 3
Required values of air gaps under switch impulse overvoltage for a 4-terminal MMC-HVDC project.
| Lines | Switching overvoltage level (p.u.) | Required 50% switching impulse discharge voltage | Altitude (m) | 0 | 1000 | 2000 |
| A-D | 1.9 p.u. | 1130 | 2.73 | 3.13 | 3.63 | C-D | 1.93 p.u. | 1147 | 2.79 | 3.21 | 3.73 | B-C | 1.9 p.u. | 1130 | 2.73 | 3.13 | 3.63 | A-B | 1.7 p.u. | 1011 | 2.4 | 2.75 | 3.2 |
|
|