A Hybrid MMC Topology with dc Fault Ride-Through Capability for MTDC Transmission System
Table 4
Parameters of the hybrid MMC-HVDC simulation system.
| Parameters | MMC1 | MMC2 | MMC3 | MMC4 |
| Rated capacity of MMC | 400 MVA | 300 MVA | 100 MVA | 100 MVA | ac bus voltage | 220 kV | 220 kV | 110 kV | 110 kV | dc bus voltage | ±200 kV | Rated capacity of transformer | 400 MVA | 320 MVA | 120 MVA | 120 MVA | Ratio of transformer | 220 kV/230 kV | 110 kV/230 kV | Leakage reactance | 0.1 pu | Bridge arm reactance | 32 mH | 55 mH | 165 mH | 165 mH | HBSMs’ number | 12 | SDSMs’ number | 4 | MCSMs’ number | 1 | SM capacitance | 3400 µF | 2550 µF | 850 µF | 850 µF |
|
|