Research Article

A Hybrid MMC Topology with dc Fault Ride-Through Capability for MTDC Transmission System

Table 4

Parameters of the hybrid MMC-HVDC simulation system.

ParametersMMC1MMC2MMC3MMC4

Rated capacity of MMC400 MVA300 MVA100 MVA100 MVA
ac bus voltage220 kV220 kV110 kV110 kV
dc bus voltage±200 kV
Rated capacity of transformer400 MVA320 MVA120 MVA120 MVA
Ratio of transformer220 kV/230 kV110 kV/230 kV
Leakage reactance0.1 pu
Bridge arm reactance32 mH55 mH165 mH165 mH
HBSMs’ number12
SDSMs’ number4
MCSMs’ number1
SM capacitance3400 µF2550 µF850 µF850 µF