Abstract

In this paper, an intelligent integrated approach is proposed to control the reactive power and restore the voltage balance in a three-phase power system using particle swarm optimization (PSO), Gaussian process regression (GPR), and support vector machine (SVM). The PSO algorithm is used in offline mode to determine the optimal set of firing angles for the thyristor-controlled-reactor (TCR) compensator according to the smallest fitness value required for voltage balancing. The optimum firing angles are then used to train the GPR and SVM regression models. The GPR and SVM models are finally used as a real-time controller to retrieve the voltage balance in online mode. A simulation model and experimental setup of the electrical power system are built. The modeled system consists of a 500 km long transmission line. The line is divided into three-pi sections to guarantee a real system response. Several simulation and practical case studies have been conducted to test and validate the capability of the proposed integrated approach in solving the voltage unbalance problem. The results have revealed the supreme ability of the proposed integrated approach to restore the voltage balance quickly (within 20 ms) and for a wide range of voltage unbalance factors (VUFs) (3.90–8.42%).

1. Introduction

Electrical power systems normally operate under balance conditions and regular three-phase voltages. In some circumstances, unbalance conditions influence the electrical power system and cause unbalance voltages. These conditions emerge when the three-phase loads are irregular or because of the asymmetries in the network topology. The unbalance voltages will inevitably degrade the performance, i.e., quality, of electrical power systems [13]. Additionally, the unbalance voltage conditions cause several system deficiencies such as electrical machine overheating, transformer overloading, high losses, and low stability of the power system [46]. The unbalance three-phase system can be decomposed into positive and negative sequence components. Several definitions for voltage unbalance are introduced. According to IEEE Std.1159–1195, the voltage unbalance is defined as the ratio between negative and positive sequence voltages [7].

Voltage balancing is critical in three-phase power systems to ensure efficient and reliable operation. Different voltage balancing techniques have been proposed to ensure that the voltages in the three phases of the system are equal, leading to better performance, improved energy efficiency, and reduced equipment damage [8]. The use of compensators such as static synchronous compensators (STATCOMs) has shown promising results in voltage balancing in three-phase power systems [911]. In the next section, an overview of recent developments and state-of-the-art techniques for voltage balancing in three-phase power systems will be presented.

2. Literature Review

Many research works have been proposed to detect and mitigate the voltage unbalance problem. The research work in [12] introduced the concept of E-STATCOMs, which are static compensator devices that include energy storage systems. The authors proposed using a supercapacitor energy storage system (SCESS) in conjunction with a STATCOM for controlling transients in a power system to improve reactive power unbalance following a contingency. The authors demonstrated that supplementary PI controllers in voltage magnitude and phase angle loops can provide extra damping to the system, leading to very good responses even under severe three-phase fault conditions. In [13], a method for controlling a 3-phase cascaded H-bridge (3ph-CHB) converter with n-levels was proposed to compensate for reactive power and eliminate the harmonic currents generated by nonlinear loads. The authors introduced a generalized model of the CHB-nL converter that takes into account the effect of the line impedance. Additionally, they proposed an advanced controller that consists of current tracking loop, to ensure that the line current tracks the reference, and outer voltage loops to ensure the regulation and balance of the capacitor voltages involved. A similar article [14] described a control scheme for a STATCOM based on a delta-connected CHB converter. The authors proposed a new feedforward control method to enhance the dynamic performance of the system. The aim of this method was to improve the regulation of zero-sequence circulating current in the delta-connected CHB STATCOM, especially during grid faults or load imbalances, without causing excessive fluctuation in the dc cell capacitor voltage. The proposed method offered significant improvements in the system’s dynamic performance. The authors in [15] also proposed a new technique for voltage regulating and balancing. The idea was regulating the three cluster voltages of a star-connected CHB STATCOM to different values, while maintaining balance in the three-phase modulation voltages. This was achieved by decomposing the positive and negative sequence components from the converter voltages to balance the three-phase currents. To ensure the stability of the cluster voltages, the authors extracted the zero-sequence voltage to analyze the active power distribution. The use of an improved model predictive control (MPC) algorithm was suggested in [16] as a means of controlling STATCOM device performance. The authors tried to forecast future STATCOM output current needed to manage designated bus line voltages in accordance with neighboring bus line voltage variations to reduce voltage imbalance. Additionally, they established the MPC state space and goal functions based on neighbors’ bus voltages, currents, and transmission line characteristics. Accordingly, the proposed method may be used for wide applications in power systems. In [17], a compensator that combines star and delta segments was proposed to eliminate neutral current, balance loads, and improve power factor. The authors derived a mathematical model based on the load current’s phase and sequence components, using symmetrical components theory for load balancing, power factor correction, and neutral current elimination. This study presented the mathematical principle for compensating a star-connected load (with neutral) that is supplied by a balanced three-phase four-wire network, using the theory of symmetrical components. The article [18] suggested a new technique to balance voltages and loads by controlling continuously variable series reactor (CVSR). In more details, by regulating the bias dc circuits of CVSR, the ac reactance was adjusted based on the nonlinear B-H characteristic of the shared ferromagnetic core. Thus, the generated dc bias magnetic flux can then be used to balance the three-phase voltages and reduce the negative impact of any imbalances on the operation and equipment of the distribution system.

The authors in [19] have proposed an algorithm for voltage unbalance detection based on Clark transformation, which converts the three-phase voltages into complex z-plane. The static volt-ampere-reactor compensative (SVC) has the ability to balance the loads and stabilize the electrical power system [2022]. The authors in [23] used the SVC to balance the load voltages and improve the power factor. The symmetrical component theory was considered to develop the mathematical model for voltage balancing. In [24], a dynamic voltage restorer technique was used together with proportional-integral (PI) controller and phase-locked loop to correct the voltage on the low voltage side. The authors in [25] used the SVC to compensate for the unbalanced three-phase four wires load. A combination of SVC and STATCOM was used to balance the three-phase load voltages in the electrical power system [14, 26]. Several factors must be considered, including accuracy and complexity when control strategies are used for voltage balancing [27, 28]. Also, the time required for algorithm computations must be taken into account. The authors in [29] used the fuzzy logic technique to train artificial neural network (ANN) which controls SVC. The controller needs more than 125 ms to retrieve the voltage balance conditions. The authors in [30] employed the ANN to retrieve the balance conditions at an average time of 60 ms for the voltage unbalance factor (VUF) range of 3.48%–4.68%. Retrieving the voltage balance conditions quickly is a necessity especially for the systems that contain time-varying loads such as electric arc furnaces. In [31], a reactive power compensator was used for this purpose. PSO algorithm is proposed in [32] to find the optimal parameters of the PI controller to retrieve the balance conditions. In [33], genetic algorithm (GA) was used for the same purpose. The GA required more than 130 ms to retrieve the voltage balance. In [34, 35], the PSO was successfully employed in electrical power system applications to retrieve the voltage balance, reduce the voltage sags, and estimate power transformer parameters. In [36], the authors compared between GA and PSO for tuning lead controllers which have three parameters to be optimized. It was concluded that the PSO has a larger mean fitness value along with the generation number compared to GA, especially when the generation continues. In [37], the authors reported some advantages of PSO over other optimization techniques, such as fewer adjustable parameters and more effective memory capability.

In conclusion, the literature review shows that reactive power control using different STATCOMs topologies is an effective strategy to retrieve the voltage balance and the stability of electrical power systems. The majority of the previously mentioned research works have been focused on controlling the reactive power to retrieve the voltage balance quickly in the three-phase power systems. This will protect the electrical equipment from long-term failures. Additionally, this is vital to enhance the system’s dynamic response. Several control techniques have been proposed to solve the problem of voltage balancing and achieve the optimal performance of electrical power systems. Machine learning-based techniques have shown promising results and have the potential to further improve the performance of voltage balancing using STATCOMs. So far, the performance of the proposed solutions is still insufficient and requires further enhancements, such as the system response time and the recovered range of VUF.

In this paper, advanced control strategy using predictive models and optimization algorithm is proposed to control a TCR and retrieve the balance conditions in three-phase power system. PSO is used in offline mode to determine the optimum set of TCR firing angles based on the VUF’s smallest fitness value. A mathematical model of a three-phase power system is used for this purpose. The modeled power system comprises a 500 km long transmission line which is divided into three-pi sections to guarantee accurate system response. GPR and SVM models are trained using the optimal firing angles determined by PSO and then used as real-time controllers to recover the voltage balance of the power system. The suggested control strategy has the ability to restore the voltage balance quickly within 20 ms and can cover a wide range of VUF 3.90–8.42%.

The paper is organized as follows: Section 3 describes the three-phase reactive power compensation in electrical power systems. The PSO algorithm and GPR and SVM models are discussed in Section 4. The mathematical model and the prototype of the electrical power system are given in Section 5. Section 6 presents the results and discussion. The contribution of this work is provided in Section 7. Finally, the conclusion of this work is given in Section 8.

3. Three-Phase Reactive Power Compensation

The main reason for using reactive power compensation in electric power networks is to maintain the stability of the power system at different loading conditions [38]. Additionally, it affords many advantages to the power system, such as voltage regulation and load balancing [21, 39]. TCR is commonly used SVC for voltage balancing [40, 41]. It consists of an inductor connected in series with two antiparallel pair of thyristors. By controlling the thyristor triggering time, the amount of inductive reactance is manipulated to generate the adequate reactive power needed for voltage balancing.

When the three-phase loads become unbalanced (i.e., imbalance of electric power flow in the three-phase load), the compensator has to generate the required reactive power to balance the three-load voltages [42]. If the load is Y-connected, the three load voltages can be calculated by using the following equation:where represent the load voltages, represent the load currents, and represent the Y-connected load impedances.

When the three-phase loads become unbalanced, the three-line currents will also become unbalanced and can be substituted by their symmetrical components as given in the following equation:where represent positive, negative, and zero sequence components of unbalanced load currents, respectively.

In equation (3), the positive, negative, and zero sequence components are indicated by the subscripts 1, 2, and 0, respectively. The zero-sequence components have no effect on the system balance because they have equal amplitude with zero phase angles from each other. To preserve the balanced three-phase load voltages, the negative-sequence components of the load currents must be eliminated. Therefore, the reactive power compensator should be used to generate the appropriate three susceptances and absorb the negative-sequence components of the load currents leading to balance load voltages. However, to obtain the adequate value of generated compensator susceptance, the TCR firing angles should be calculated accurately. Consequently, an advanced real-time control using GPR and SVM is proposed in this work to perform the previous duties, i.e., calculate the TCR firing angles and retrieve the balance conditions of the electrical power system. Figure 1 shows the proposed controller that utilizes GPR and SVM algorithms to control the reactive power compensator and retrieve balance conditions.

4. The Proposed Integrated Approach

In this work, an advance integrated approach is proposed to control the reactive power and restore the voltage balance in three-phase power systems using the PSO algorithm and SVM-GPR models. The proposed approach can be divided into three stages. In the first stage, the PSO algorithm is used to determine the optimum set of TCR firing angles, using the steady-state mathematical model of the power system. This stage is executed only in offline mode because using the PSO in online mode will degrade the system’s dynamic behavior. This is due to the iterative nature of the PSO computation. Therefore, in the proposed integrated approach, the GPR and SVM are used to control the system in online mode. In the second stage, the optimum firing angles calculated from the PSO in the offline mode are appointed to train the GPR and SVM models. Finally, in the third stage, the GPR and SVM models are used as a real-time controller to restore the voltage balance in online mode.

4.1. Particle Swarm Optimization (PSO) Algorithm

Particle swarm optimization (PSO) was proposed in 1995 by Kennedey and Eberhart. PSO algorithm simulates the swarm behavior in nature. It searches a space of dimension (d) by moving a swarm that consists of n-particles to determine the best solution based on a fitness function. Every particle in the swarm has its own position and velocity [43].

The algorithm starts searching the space of dimension (d) by initializing a swarm with (n) particles, randomly. Then, each particle modifies its position according to its fitness and the fitness of the neighborhood particles as well. The fitness of the particle is evaluated according to the defined cost function to assign the best particle among the current generation which is called the personal best particle (pbest). Pbest is the local particle in the swarm that has the minimum fitness value within the same position in the swarm [44, 45]. The global best particle (gbest) of the smallest fitness is found by comparing the fitness values of all personal best particles. In each iteration, the velocity and position of the particles are updated according to equations (4) and (5), respectively [36]. PSO algorithm continues searching in the d-dimensional space until one termination condition is achieved.wherewhere represents inertia factor. c1 and c2 represent random integers (between 2 and 4). r1 and r2 represent random numbers (between 0 and 1). Pbest represents personal best particle. represents the velocity of the nth particle in a space of dimension (d). Xnd represents nth particle in a space of dimension (d). represents global best particle. rand represents random number (0-1). iter represents sequential number of iterations.

One of the most important aspects when utilizing the PSO algorithm is defining an appropriate fitness function to measure the quality of the solutions. In this paper, the proposed fitness function relies on the VUF of the three-phase load voltages to get the optimal particle that has the smallest fitness value (i.e., smallest VUF).

Figure 2 shows the flowchart of the first stage in the proposed approach. In this stage, the PSO algorithm is used with the mathematical model of a 500 km long electrical power system to find the TCR optimal firing angles required for voltage balancing. The PSO particles represent the TCR firing angles, αab, αbc, and αca. The PSO operates when an unbalance load change is detected. The following steps summarise the first stage of the proposed integrated approach.(1)Strat PSO algorithm by generating a random swarm with n-particles and their velocities. In this paper, the particles and their velocities are given by the following equations, respectively:where Xn3 represents nth particle in a space of 3-dimension (i.e., 3-firing angles of TCR).  Vn3 represents the velocity of the nth 3-dimension particle. αab, αbc, and αca represent the firing angles of TCRs.   represent the velocities of the three components of the particle.(2)Evaluate the three-phase load voltages that correspond to each particle using the mathematical model of the 500 km long electrical power system, and then calculate the fitness (J) of each particle using the following equation:where   represents the positive-sequence voltage and   represents the negative-sequence voltage.(3)Find pbest according to the minimum value of fitness (at a minimum value of VUF).(4)Compare the fitness values of all personal best particles and assign the one with the smallest fitness as the global best particle (gbest).(5)Update the velocities and particles using equations (4) and (5), respectively.(6)Repeat steps 2 to 5 until the fitness of VUF for three-phase voltages becomes less than 2%.(7)Apply the best particle which corresponds to the minimum VUF on the TCR compensator.

4.2. Gaussian Process Regression and Support Vector Machine

The Gaussian processes are probabilistic supervised-machine learning methods that have been extensively utilized in statistical modeling, regression, and pattern classifications [46]. The GPR model performs predictions joining prior knowledge and provides uncertainty measures over predictions [47]. In other words, GPR is a nonparametric kernel-based probabilistic model with a finite collection of random variables with a multivariate distribution. The Gaussian processes have many advantages, such as interpolate observations, adaptive fitting, and kernel versatility. The key points in the GPR can be summarized as follows: Firstly, the next function is updated with new observations. Secondly, finite samples of functions are jointly-Gaussian distributed. Finally, the mean function which is calculated by the posterior distribution of possible functions is used for regression predictions. The regression function modeled by a multivariate Gaussian is given as follows [48]:where X = [x1, . . ., xn]. X is the observed data points. f = [f (x1), . . ., f (xn)] and μ = [m (x1), . . ., m (xn)]. m is the mean function, Kij = k (xi, xj). k is a positive definite kernel function.

Support vector machine is a regression and classification tool that uses machine learning theory to increase predictive accuracy and avoid data overfitting problems [48]. SVM uses the hypothesis space of linear functions in a high-dimensional feature space. Additionally, SVM is trained with a learning algorithm from optimization theory that implements a learning bias derived from statistical learning theory [49]. Duality, kernels, convexity, and sparseness are the most major features of SVM, it is one of the best approaches for data modeling and combines generalization control as a technique to control dimensionality. It has been proved that the SVM has the upper hand over the neural network (NN) in regression due to many reasons [50]. SVM gives higher accuracy in comparison with sophisticated neural networks with elaborated features in regression tasks. Additionally, SVM performs better in terms of not overgeneralization when the neural networks might end up overgeneralizing easily [49].

5. The Mathematical Model and the Prototype of Electrical Power System

To test the performance of the proposed integrated approach, an electrical power system with a long transmission line is considered and modeled. The general mathematical model was derived in [28] and use in this work for a 500 km long transmission line. This power system consists of a 15 kV 3-phase generator, a step-up transformer at the generator side, step-down transformers at the load side, a 500 km long transmission line divided into three-pi sections, and delta connected load. Table 1 shows the components specifications in the modeled power system. The mathematical model of the power system is generated, built, and simulated using MATLAB SIMULINK. Figure 3 shows the block diagram of the modeled power system with the PSO algorithm. Moreover, an experimental setup of the power system prototype is built to support the simulated results and validate the ability of the proposed integrated approach in retrieving the voltage balance conditions successfully. The prototype consists of the following equipment: three-phase voltage source of 178 V, the equivalent transmission line divided into 3 π-section networks, three-phase inductive load, and data acquisition (DAQ) device. The experimental setup is shown in Figure 4.

6. Results and Discussions

As mentioned in Section 3, the proposed approach is divided into three stages. In stage one, the PSO algorithm is used to determine the optimum set of TCR firing angles in offline mode. These firing angles are used in stage two to train the GPR and SVM models. In the third stage, the GPR and SVM models are used as real-time controllers to retrieve the voltage balance. Accordingly, in this section, the results and discussions will be introduced for each stage individually.

6.1. The Results and Discussion in Stage One

Many unbalance cases were created to evaluate the ability of the proposed PSO algorithm for restoring the voltage balance in the load side of the system. Table 2 shows the results for different loading conditions covering a wide range of VUF. Table 2 includes the VUF values before and after PSO action, the optimal firing angles generated by the PSO algorithm, and the time needed to retrieve the balance conditions measured from the PSO initiating time. As indicated in Table 2, the average value of VUF after activating the PSO is 0.717% which is lower and better than the recommended value (i.e., 3%). Thus, the results prove the capability of the proposed PSO algorithm in recovering the system balance conditions and achieving very low VUF values. In addition, it can be noted from Table 2 that the time needed by the PSO to retrieve the system balance conditions in some cases exceeded 30 ms. This long delay in the PSO response will degrade the system’s dynamic behavior. Consequently, the PSO is used in the offline mode only.

6.2. The Results and Discussion in Stage Two

The optimum set of TCR firing angles generated by the PSO in stage one was used to train GPR and SVM models. The input data for these models are the three load unbalance voltages and the VUF, while the output data of these models are the three firing angles of the TCR compensator needed for voltage balancing. The performance of the trained GPR and SVM models is shown in Figures 5 and 6, respectively. The regression factor (R2), which indicates the model’s ability to produce the desired output, is 0.95 and 0.93 for GPR and SVM models, respectively. The root mean square error (RMSE), which shows the model’s ability to track the data points, is 0.084772 and 0.099518 for GPR and SVM, respectively. The results show that the GPR and SVM models have the ability to track the data points and produce the desired output efficiently. However, at this stage, the GPR model introduced a slightly better performance than the SVM.

6.3. The Results and Discussion in Stage Three

Several tests were conducted to demonstrate, assess, and validate the feasibility and effectiveness of the proposed integrated approach in restoring the system voltage balance. During these tests, the three loads were changed deliberately and asymmetrically to create a wide range of unbalanced voltages. The tests were conducted using both the simulation and practical models.

Three tests were conducted using the simulation and practical models. The first and second tests were conducted using the simulation model, while the third test was conducted using the practical model. In the first test, many unbalance cases were created to test the ability of the GPR and SVM models in recovering the voltage balance for different loading conditions covering a wide range of VUF. Tables 3 and 4 show the results of this test when using GPR and SVM models, respectively. These tables include the TCR firing angles generated by GPR and SVM models, the VUF values, and the three load voltages before and after the model’s action. It can be noted from these tables that the average value of VUF before the model’s actions is 6.002%. As indicated in Table 3, the average value of the VUF is reduced to 0.580% by using the GPR model. While, as indicated in Table 4, the SVM reduced it to 2.041% which is lower and better than the recommended value (i.e., 3%). Thus, the results in Tables 3 and 4 prove the capability of the GPR and SVM models in recovering the system balance conditions efficiently and achieving very low VUF values. Additionally, the results revealed that the GPR outperforms the SVM by achieving low VUF values.

In the second test, an unbalance case was created to assess the system time response and demonstrate the three-phase load voltages. The test case scenario is as follows: starting the electrical power system with balanced conditions during the time interval from 0 to 0.1 sec, then making unbalance change in the three-phase loads exactly at 0.1 sec, and finally initiating the GPR or SVM controller at 0.15 sec. Figures 7 and 8 illustrate the effect of GPR and SVM controllers, respectively, on the three load voltages when the VUF is 6.985%. It is noted that the GPR and SVM controller recovered the balance conditions of the power system accurately within a very narrow time interval. Additionally, The VUF is reduced from 6.985% to 0.842% and from 6.985% to 1.752% using GPR and SVM, correspondingly.

In the third test, which was conducted using the practical model, another unbalance case was created to validate the simulation results in the second test. The unbalance change in the three-phase loads is initiated at 0.05 sec, and GPR or SVM controller is activated at 0.1 sec. Figures 9 and 10 illustrate the effect of GPR and SVM controllers, respectively, on the three load voltages when the VUF is 5.69%. It can be observed from these figures that the GPR and SVM controllers recovered the balance conditions of the power system accurately within a very narrow time interval. Additionally, The VUF is reduced from 5.69% to 1.64% and from 5.69% to 2.03% using GPR and SVM, correspondingly. In conclusion, the results from the three tests proved the ability of the proposed integrated approach to balance the three-load voltages quickly and achieving very low VUF values.

7. Contribution to Knowledge

Table 5 introduces a brief comparison between the state-of-the-art techniques for voltage balancing in three-phase power systems mentioned in Section 3 and the proposed integrated approach. Accordingly, the contributions of knowledge in this paper are as follows:(1)In the proposed integrated approach, GPR and SVM models are trained using the optimum data set of firing angles generated from the PSO algorithm. These firing angles are required to drive the TCR compensator and restore the voltage balance in the three-phase power system. These optimum values enhanced the performance of the trained GPR and SVM models and achieved high R2 factor and low RMSE.(2)The proposed integrated approach retrieved the balanced conditions in the electrical power systems successfully by achieving a fast response time of only 20 ms. Indeed, this is the shortest response time among the methods proposed in the literature. Therefore, the proposed approach enhanced the system’s dynamic behavior.(3)The proposed integrated approach can solve the voltage unbalance problem and cover a wide range of VUF between 3.90% and 8.42%. This VUF range is wider than the ranges achieved in the literature.(4)The proposed integrated approach obtained the best performance for a three-phase power system and restored the voltage balance at an average VUF of 0.580%

8. Conclusion

In this paper, an advance integrated approach is proposed to control the reactive power and restore the voltage balance in three-phase power systems using the PSO algorithm and SVM-GPR models. The PSO algorithm is used to determine the optimum set of TCR firing angles required for voltage balancing in offline mode, these firing angles are then used to train the GPR and SVM regression models; finally, the models are used as a real-time controller to restore the voltage balance in the online mode. Simulation and physical models for the electrical power system were built. In addition, three tests with different unbalance cases were conducted to validate the proposed integrated approach. The results have revealed the superiority of the proposed advanced approach over others mentioned in the literature and the ability of this approach to retrieve the voltage balance conditions quickly (within 20 ms) with a wide range of VUF (3.90–8.42%).